Trident®-S

Trident®-S is a three phase, spring-assisted load break or fault interrupting switch. Its side-mounted handles can be positioned with a hookstick eye on top or bottom, providing the ideal mechanical advantage for either vertical or horizontal mounting.

Configure Your Product Email your specs

Features and Benefits

Ratings Chart for Trident Spring-operated Switchgear

Voltage Class (kV)152535*
Max. System Voltage (kV)15.5‡27†38
BIL (kV)110125150
Continuous Current (A)630§630§630§
Load Break Current (A)630§630§630§
AC Withstand, 1 min. (kV)356070
AC Withstand, Productions, 1 min. (kV) 344050
DC Withstand, 15 min.5378103
Momentary Current, RMS, Asym (kA) 202020
Fault Close 3 Times, Asym (kA) 202020
Current, Sym (kA), 1 Sec. 12.512.512.5
Fault Interrupting Current, Sym (kA)12.512.512.5
Vacuum Interrupter Mechanical Operations2,0002,0002,000
Note:
§ Up to 900A available on In/Out ; Up to 800A available on multiway Trident without SafeVu
* 35kV not applicable for Trident-SP
† Models available up to 29.3kV
‡ Trident-S with SafeVu feature limited to 95kV BIL
Product Literature

Spring Operated Trident® Switchgear

Download

Trident Product Family

Download
Case Studies

Oil Fuse Cutout Replacement w Solid Dielectric Switchgear

Download

Underground Circuit Protection and Sumbersible Switchgear

Download

Military Base Closed Loop Restoration

Download
Application Guides

Submersible Switchgear Applications

Download
Specifications

ATC Trident padmount (front access style) Specification

Download

Multi-way 3-phase front access Compact Trident Specification

Download

Multiway Trident 3 phase (front access) Specification

Download

Multiway Trident 3 phase padmount (air gear style) Specification

Download

2-way 3 phase Trident®-S fault interrupting switch Specification

Download

2-way 3 phase-Trident®-SafeVu Fault Interrupter

Download

2-way 3 phase Trident® with SafeVu Load Break

Learn More

Multiway Trident with SafeVu Front Back Guide

Download

Multiway Trident with SafeVu Front Access Guide

Download